450/750V PVC insulated wire (IV)
Usage
- Used for indoor distribution line under AC 450/750V grade
Applied specification
- KS C IEC 60227-3
Structure
- Conductor : Annealed copper wire (Tinned annealed stranded area and smaller are acceptable)
Hard-drawn aluminum or half hard-drawn aluminum wire
- Solid conductor : 1 class
- Stranded conductor : 2 class - Insulation : PVC/C
- Color or the insulation : Black (If necessary, black, white, red, green, yellow, blue)
- Maximum allowable temperature : 70℃
60227 KS IEC 01 (IV)
Conductor & Nominal Sectional Area |
Conduct Class (KSC IEC 60228) |
Insulation Thickness (Standard) |
Standard Overall Diameter | Min. Insulation Resistance at 70℃ |
|
---|---|---|---|---|---|
Min. | Max. | ||||
㎟ | ㎜ | ㎜ | ㎜ | ㎜ | MΩ-㎞ |
1.5 | 1 | 0.7 | 2.6 | 3.2 | 0.011 |
1.5 | 2 | 0.7 | 2.7 | 3.3 | 0.010 |
2.5 | 1 | 0.8 | 3.2 | 3.9 | 0.010 |
2.5 | 2 | 0.8 | 3.3 | 4.0 | 0.009 |
4 | 1 | 0.8 | 3.6 | 4.4 | 0.0085 |
4 | 2 | 0.8 | 3.8 | 4.6 | 0.0077 |
6 | 1 | 0.8 | 4.1 | 5.0 | 0.0070 |
6 | 2 | 0.8 | 4.3 | 5.2 | 0.0065 |
10 | 1 | 1.0 | 5.3 | 6.4 | 0.0070 |
10 | 2 | 1.0 | 5.6 | 6.7 | 0.0065 |
16 | 2 | 1.0 | 6.4 | 7.8 | 0.0050 |
25 | 2 | 1.2 | 8.1 | 9.7 | 0.0050 |
35 | 2 | 1.2 | 9.0 | 10.9 | 0.0040 |
50 | 2 | 1.4 | 10.6 | 12.8 | 0.0045 |
70 | 2 | 1.4 | 12.1 | 14.6 | 0.0035 |
95 | 2 | 1.6 | 14.1 | 17.1 | 0.0035 |
120 | 2 | 1.6 | 15.6 | 18.8 | 0.0032 |
150 | 2 | 1.8 | 17.3 | 20.9 | 0.0032 |
185 | 2 | 2.0 | 19.3 | 23.3 | 0.0032 |
240 | 2 | 2.0 | 22.0 | 26.6 | 0.0032 |
300 | 2 | 2.4 | 24.5 | 29.6 | 0.0030 |
400 | 2 | 2.6 | 27.5 | 33.2 | 0.0028 |